InfiniBand error counters: read deltas, not totals

Port counters are cumulative since the last reset, so a large number may be five years of history and a small one may be happening right now. Only a delta over a known window tells you whether a link is degrading.

Archive date is an editorial placement, not the original publication date. Published 17 October 2026; documentation reviewed 17 October 2026. Examples describe proposed checks, not customer incidents or measured product results.

Someone runs a fabric error sweep, finds a port with a symbol error count in the millions, and schedules a cable replacement. The count is real. It may also be the accumulated total since the switch was commissioned four years ago, in which case the cable is fine and the maintenance window is wasted.

Error counters on InfiniBand ports are cumulative since last reset. A total is close to uninterpretable on its own.

The only reading that means anything is a delta

Take two samples with a known interval between them and subtract.

# sample, wait, sample again
ibqueryerrors --counters > /tmp/err.t0
sleep 900
ibqueryerrors --counters > /tmp/err.t1

Or reset deliberately and come back:

perfquery -R -a                 # reset all counters on all ports
# ... run a representative load for a known period ...
perfquery -a | grep -vE ' 0$'   # anything non-zero accumulated in that window

Resetting is the cleaner experiment and the one to prefer before a benchmark or an acceptance test: a window that starts at zero needs no arithmetic and no trust in a previous sample. The cost is that you have destroyed the history, so capture it first if anyone might want it.

What you are looking for is rate per unit time on a link carrying traffic. A handful of symbol errors over fifteen minutes of heavy traffic on an NDR link is not interesting. The same count on an idle link is, because the mechanism had almost no opportunity.

That asymmetry is why the sweep should record whether the link was loaded. “Zero errors” on a fabric nobody is using is not a result.

Which counters carry which meaning

Not all non-zero counters imply the same thing, and conflating them produces both false alarms and missed faults.

Counter Reads as Typical cause
SymbolErrorCounter Physical layer noise Cable, connector seating, transceiver, bend radius
LinkErrorRecoveryCounter Link retrained and recovered Marginal physical layer
LinkDownedCounter Link went fully down Reseat, power event, port flap, firmware
PortRcvErrors Malformed or corrupted inbound packets Usually downstream of symbol errors
PortXmitDiscards Packets dropped at egress Congestion or credit starvation, not a cable
PortXmitWait Time waiting for credits Congestion; routing imbalance; a slow endpoint
VL15Dropped Management packets dropped SM load, or a genuinely saturated port
ExcessiveBufferOverrunErrors Flow control problem Mismatched MTU/credits, firmware

The important split: the first four are physical; PortXmitDiscards and PortXmitWait are architectural. A port with high XmitWait and zero symbol errors does not have a cable problem — it has more demand than credits, and replacing the cable will change nothing. That is the single most common misdiagnosis in this area, because both appear in the same error sweep output under the same heading.

High XmitWait concentrated on inter-switch links is a routing or provisioning finding: the links are being asked to carry more than they can, or the routing algorithm has put more traffic on some of them than others. That is a topology conversation, not a hardware one.

Separate from counters, a link can negotiate a lower width or rate and sit there perfectly healthy, with zero errors, reporting Active. Four lanes becoming one is a 4x bandwidth loss with no error counter movement at all.

iblinkinfo | grep -vE '4X +(53|106|212)'      # anything not 4X at the expected per-lane rate

Two traps in reading that output, both of which produce wrong capacity conclusions:

  • The rate field is per lane. 106.25 Gbps on a 4X link is NDR400, not 106 Gbps of link capacity. Multiply by the width.
  • Width is reported as 1X/2X/4X and a 2X link looks almost identical to a 4X one in a quick scan. grep for what you expect rather than eyeballing a long listing.

Why this matters more than the error count: on a synchronized collective, the job proceeds at the speed of its slowest participant. One node at half width sets the time for every rank. So a single silently degraded link can look exactly like a fabric-wide bandwidth problem, and chasing it as a fabric problem — tunables, routing, firmware — can absorb days. Check every participant’s width and rate before you accept any synchronized benchmark number. A withdrawn performance claim is the usual price of skipping it.

Build the sweep so it can be compared

An error sweep is only useful against a baseline, so the output needs to be diffable.

#!/bin/bash
# one line per port, stable field order, so two runs can be diffed
set -uo pipefail
OUT=${1:-/var/log/ibsweep/$(date +%Y%m%d-%H%M).tsv}
mkdir -p "$(dirname "$OUT")"
ibqueryerrors --counters --data 2>/dev/null \
 | awk '/^Errors for/ {gid=$NF} /Counter/ {print gid"\t"$0}' > "$OUT"
echo "$OUT"

Then the operational question becomes a diff rather than a judgement:

diff <(cut -f1,2 baseline.tsv) <(cut -f1,2 "$OUT") | head -40

Two further practices that make the sweep trustworthy:

  • Record the window and the load. A sweep row without “15 minutes, under IOR” next to it cannot be compared with anything.
  • Alert on the delta, not the total. A threshold on a cumulative counter fires once and then fires forever, which trains everyone to ignore it.

An order of operations

  1. Capture the current totals, so history is not lost.
  2. perfquery -R -a to reset.
  3. Confirm width and rate on every link you care about — this is independent of counters and catches the silent case.
  4. Run a representative load for a fixed period.
  5. Re-read counters. Anything non-zero accumulated inside a known window with known load.
  6. Split the findings: physical counters to hardware, XmitWait/Discards to topology.
  7. Re-seat or replace one thing at a time, and repeat the windowed measurement. A fix is a counter that stays at zero through a load, not a counter you just reset.

Step 7’s last sentence is where most of the remaining errors come from: resetting a counter and observing zero proves only that you reset it.

Symptom against cause

Symptom Likely reading Next step
Huge symbol error total, link stable Years of accumulation reset, re-measure under load
Errors climbing on an idle link Genuine physical fault reseat, then swap cable
High XmitWait, zero symbol errors Congestion or routing imbalance topology, not cabling
LinkDowned incrementing Flapping check both ends, power, firmware
Zero errors, poor collective performance A link at reduced width or rate iblinkinfo, mind per-lane rate
Clean sweep, no traffic during it The window had no load repeat under load

A counter is a total, and a total is not a symptom. Give every number a window and a load before you let it justify a maintenance action.